a. Z1S MHO with reactance X
Z1S-DX.Angle
Z1S-R.Angle
Z1S-Mho.angle
Z1S-R.Reach (in the left)
Figure 2.1-12 Zone1 MHO element set with reactance X in forward direction
Quad characteristic
Figure 2.1-13(a) and (b) show the Z*S and the Z*G used in the Quad characteristics. For
example, the reach of Z*S (top line) is defined by reactance X and the reach value should be
set for the scheme switch [Z*S-X.Reach]. A resistive element (left line) and a directional
element (bottom line) can be set by the settings [Z*S-DX.Angle] and [Z*S-DR.Angle]
respectively. The resistive elements (right and left lines) can be configured by the settings [Z*S-
R.Reach] and [Z*S-R.Angle]; the blinder (left line) is used to cut the area of the Quad
characteristic by applying settings [Z*S-R.Reach] and [Z*S-R.Angle].
The 'knee' function is configured by the settings [ZSF-X.GrAngle1] and [ZSF-X.GrAngle2].
When On-Adapt is set for the scheme switch [ZS-X.GrAngleEN], the 'knee' function operates
when power flow is detected, similar to the MHO element.
a. Z1S Quadrilateral
Z1S-X.Reach
Z1S-R.Angle
Z1S-DX.Angle
Z1S-R.Reach (in the left)
Figure 2.1-13 Zone1 Quadrilateral element in forward direction
X
Z1S-X.Reach
ZSF-X.GrAngle1
ZSF-X.GrAngle2
Z1S-R.Angle
Z1S-R.Reach (in the right)
X
ZSF-X.GrAngle1
ZSF-X.GrAngle2
Z1S-R.Angle
R
Z1S-DR.Angle
Z1S-R.Reach (in the right)
Z1G-DX.Angle
Z1G-R.Angle
R
Z1G-Mho.angle
Z1G-R.Reach (in the left)
a. Z1G Quadrilateral
Z1G-X.Reach
Z1G-R.Angle
Z1G-R.Reach (in the left)
- 38 -
6F2S1915 (0.46)
b. Z1G MHO with reactance X
X
Z1G-X.Reach
ZGF-X.GrAngle1
ZGF-X.GrAngle2
Z1G-R.Reach (in the right)
X
ZGF-X.GrAngle1
ZGF-X.GrAngle2
Z1G-R.Angle
Z1G-DR.Angle
Z1G-DX.Angle
Z1G-R.Reach (in the right)
GRZ200 (Soft 031 & 032)
Z1G-R.Angle
R