Download Print this page

Toshiba GR200 Series Instruction Manual page 679

Hide thumbs Also See for GR200 Series:

Advertisement

map the input-point to the Object references having attributes CO and CF† . Figure 4.4-16 shows
how to map a signal.
†Note: The attribute is defined in the IEC 61850; "CO" stands for "Control" and "CF"
stands for "Configuration" in the functional constraint (FC).
Table 4.4-6 Mapping signals required for SPCSO object of GGIO3302
Object_reference
Ctrl/GGIO3302$SPCSO1$Oper
Ctrl/GGIO3302$SPCSO1$Oper
Ctrl/GGIO3302$SPCSO1$Oper
Ctrl/GGIO3302$SPCSO1$Oper
Ctrl/GGIO3302$SPCSO1$Oper
Ctrl/GGIO3302$SPCSO1$Oper$origin
Ctrl/GGIO3302$SPCSO1$Oper$origin
Ctrl/GGIO3302$SPCSO1
Ctrl/GGIO3302$SPCSO1
Check "Input"
Attribute
Type
ctlVal
BOOLEAN
ctlNum
INT8U
T
Timestamp
Test
BOOLEAN
Check
Check
orCat
orCategory
orIdent
Octet64
ctlModel
ctlModel
sboClass
sboClass
Figure 4.4-16 Input-point mapped for GGIO3302
- 658 -
FC
Signal Number
CO
CO
CO
CO
CO
529001 700C016D08
CO
CO
CF
CF
6F2S1915 (0.46)
Signal Name
OPTR01_CONTROL_REQ
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200