Wait for a command
Select stage
Select command On from the remote-end
Select command Off from the remote-end
Select command On from the local-end
Select command Off from the local-end
Select command On by the PLC function
Select command Off by the PLC function
Input signal generated at the local-end.
Figure 4.1-24 illustrates the operate logic when an "Operate command On (Local-ON-Control)"
signal is applied to the SPOS01 function. The signal is generated when "Execution of On" is
keyed on the IED front panel.
Input
Command "Local-On-Control"
ILK† condition ("ON") passed
SPOS01-On
ILK† bypassing ( Bypass)
ICB_STATE
User configurable condition (PLC#1 connection point)
510001 810101EE57
SPOS01IN_TMP_35
User configurable condition (PLC#2 connection point)
510001 810101EDDA
SPOS01IN_TMP_42
ASEQ function§" is in progress
ASEQ_MULTI_SEL
†Note: The ILK function provides the operation criteria for "On".
Wait for a next command
Operate command On from the local-end
Operate command Off from the local-end
Operate command On from the local-end
Signal reception from
the front panel
Operate command Off from the local-end
Operate command On by the PLC function
Operate command Off by the PLC function
Figure 4.1-23 Outline of operate command 'On'
Operate logic in SPOS01
SPOS1 function (Function ID: 510001)
Operate Cmd.
with ILK
condition
&
Operation Cmd.
without ILK
condition
1≥
[SPOS01-LGCTRCON]
Fixedlogic
Operate condition‡
[SPOS01-LGCFEXOT]
Fixedlogic
[SPOS01-PLSM]*
Var
Fix
Latch
"SPOS01-EX_CMP"
(5A0101_8001011E93)
"SPOS01-FEX_BO"
(510001_8101011DD0)
Figure 4.1-24 Operate 'On' on the front panel
- 522 -
Operation
Operate logic
Failed
"
SPOS01-OEC_OK_CSF"
(510001_8001011E7F)
1≥
1≥
&
&
&
&
&
PLC#1
6F2S1915 (0.46)
Success
Signal output
decision
Do nothing
Output
[SPOS01-CPW]
1≥
0.1 – 50.0 s
S
R
S
R
To BO connection
"SPOS01_OEX_BO"
(510001_8201011DD3)
&
Assign to BOs
&
PLC#2
To "Wait for a command"
"
SPOS01_EX_FFL
[SPOS01-RST]
(510001_8601011E91)
0
t
1.0s- 100.0s
Operation Failed
GRZ200 (Soft 031 & 032)
§§
To PLC
logic
"
††