Download Print this page

Toshiba GR200 Series Instruction Manual page 942

Hide thumbs Also See for GR200 Series:

Advertisement

Binary IO module (BI, BO, and BIO)
Binary IO modules are provided in the IED to signal a command for external devices. Binary
IO modules are also used to receive status information. Binary IO modules are connected to
external devices with signal wires using terminal blocks on the rear of the IED. There are
standard type and variable type in Binary IO modules as shown in Table 5.4-1.
Module
Module
#
name
Type
3
4
1
BI1A
Standard
2
BI2A
Variable
3
BI3A
Standard
4
BO1A
Standard
5
BO2A
Standard
6
BIO1A
Standard
7
BIO2A
Standard
8
BIO3A
Standard
Note:
1
Note:
2
Note:
3
Note:
4
Table 5.4-1 Number of input and output circuits
Number of
input
Fast
circuits
operating
18
0
12
0
32
0
0
0
0
0
7
0
12
0
8
6
PWS module supplies a DC voltage for binary IO modules: 48Vdc or 220Vdc.
Hence, the BIOs output circuits operate with the supplied DC voltage. Dual
voltages output (i.e., 48Vdc and 220Vdc) is not possible in the binary IO
modules.
For the structure and the number of binary IO modules, see section 5.4.5.
For details of the output circuits, see Table 5.4-8.
For the binary input circuits in the standard type, the user can choice either
a high voltage or a low voltage with regard to the input threshold. For the
ones of the variable type, the user itself can set a threshold value with regard
to input voltage using settings.
- 921 -
Number of output circuits
Semi-fast
Hybrid
operating
0
0
0
0
0
0
6
0
0
16
6
0
3
0
0
0
6F2S1915 (0.46)
1
2
Auxiliary
Form C
(Normal)
0
0
0
0
0
0
12
0
0
0
3
1
1
1
1
1
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200