Function setup
4.11.1
Figure 4.11-1 outlines the command reception in the ASEQ01 function. The ASEQ01 function
can generate a start command at the PLC monitoring point "ASEQ01_EXEC_START" (see
Table 4.11-5), when the start command is provided for the 'ASEQ01_CONTROL_REQ'.
Similarly, when a stop command is received in the ASEQ01 function, the stop command will
be generated at the PLC monitoring point "ASEQ01_EXEC_STOP" (see Table 4.11-6) †.
†Note: Create "IN1" and "IN2"points in the user programming logic; make the connection
between the ASEQ01 function and the user programing logic. Refer to chapter
PLC function
For example, if the user wishes to control a CB using the logic, the logic should
have two output points for two binary output circuits (BOs). Figure 4.11-1 shows
how two BOs are used for CB closing and CB opening.
‡Note: The ASEQ01 function does not have the responsibility to restart the programmed
logic after an emergency stop signal has been applied. Therefore, the user should
program the logic to generate an operation result signal in case of the emergency
stop signal being applied in the logic. See section 4.11.5 for the emergency
operation.
‡Note: PLC connection point "ASEQ01_EXEC_RESET" is provided for stopping the
ASEQ01 operation, as shown in Table 4.11-4.
IED
523001 700D016D08
Remote operation
523001 820D10ED50
IED front panel
operation
"Reply Signal"
"Emergency stop"
523001 800D01EDF2
Figure 4.11-1 ASEQ01 controls the user programing logic to operate a CB
Table 4.11-2 Mapping points for the r remote control commands
Signal Number
Signal Name
523001 700D016D08
ASEQ01_CONTROL_REQ
523001 700D026D08
ASEQ02_CONTROL_REQ
523001 700D036D08
ASEQ03_CONTROL_REQ
...
...
523001 700D0F6D08
ASEQ15_CONTROL_REQ
. The user-programming logic is also required to have output points.
ASEQ01
In
Out
ASEQ01_
ASEQ01_CONTROL_REQ
EXEC_START
EMERSTOP_CONTROL_REQ
ASEQ01_
EXEC_STOP
EMERSTOP_
EXEC_STOP
ASEQ01-EXEC_RESET
- 874 -
User programming logic for
CB control
logic
Xxxxxx 8xxxxxxxxx
IN1
Xxxxxx 8xxxxxxxxx
IN2
Description
ASEQ01 control command received. (Mapping Data)
ASEQ02 control command received. (Mapping Data)
ASEQ03 control command received. (Mapping Data)
...
ASEQ15 control command received. (Mapping Data)
6F2S1915 (0.46)
In
Out
Binary Output
4
Circuit
OUT1
Driver
Binary Output
OUT2
4
circuit
Driver
GRZ200 (Soft 031 & 032)
Device
Close
Open
M/O
M
M
M
M