Download Print this page

Toshiba GR200 Series Instruction Manual page 191

Hide thumbs Also See for GR200 Series:

Advertisement

OC (Function ID: 440001)
Setting items
ORG
OC3
OC3-DPR
OC3-TMS-ORG
OC3-Rtimer
TOC3R
OC3-RTMS-
ORG
OC3-k
OC3-a
OC3-c
OC3-kr
OC3-b
Output
OC3-2fBlk
OC3-VTFBlk
OC3-OPMD
OC3-UseFor
OC3-ARCBlk
OC4
OC4-Dir
OC4-Angle
OC4-Timer
DT
OC4
OC4-DPR
TOC4
IEC
OC4
OC4-DPR
OC4-TMS-IEC
TOC4R
UK
OC4
OC4-DPR
OC4-TMS-UK
TOC4R
IEEE
OC4
OC4-DPR
OC4-TMS-
IEEE
OC4-Rtimer
TOC4R
OC4-RTMS-
IEEE
US
OC4
OC4-DPR
OC4-TMS-US
Range
Unit
1A rating
5A rating
0.02 -
0.10 -
A OC3 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC3 drop-out/pick-up ratio
0.010 - 50.000
- OC3 time multiplier of ORG inverse curve
DEF / DEP
- OC3 reset delay type of US
0.00 - 300.00
s OC3 definite time reset delay
OC3 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
0.00000 - 500.00000
- OC3 user original curve coefficient
0.00000 - 10.00000
- OC3 user original curve coefficient
Non / Block-3P /
- OC3 operation block by 2f-detection
Block-PerP
Non / Block
- OC3 operation block by VTF
3POR / 2OUTOF3
- OC3 operation mode
Trip / Alarm
- OC3 used for trip or alarm
Non / Block
- Autoreclose block by OC3
NonDir / Forward /
- OC4 directional characteristic
Reverse
0 - 180
deg OC4 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC4 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 -
0.10 -
A OC4 threshold (in DT mode)
50.00
250.00
10 - 100
% OC4 drop-out/pick-up ratio
0.00 - 300.00
s OC4 operating delay time (in DT mode)
0.02 -
0.10 -
A OC4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of IEC inverse curve
0.00 - 300.00
s OC4 definite time reset delay
0.02 -
0.10 -
A OC4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of UK inverse curve
0.00 - 300.00
s OC4 definite time reset delay
0.02 -
0.10 -
A OC4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of IEEE inverse curve
DEF / DEP
- OC4 reset delay type of IEEE
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 -
0.10 -
A OC4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of US inverse curve
- 170 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
1.00
5.00
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
3POR
Trip
Block
NonDir
45
DT
1.00
5.00
100
1.00
1.00
5.00
100
1.000
0.00
1.00
5.00
100
1.000
0.00
1.00
5.00
100
1.000
DEF
0.00
1.000
1.00
5.00
100
1.000

Advertisement

loading

This manual is also suitable for: