Figure 4.2-54 exemplifies the SPOS logic node saved as "CSWI1". In the DIR mode, the
following three items should be selected using GR-TIEMS.
Figure 4.2-54 LN editing screen for DIR mode
Mapping output data
(ii)
The user should group the DPSY01 signals with regard to GOOSE and REPORT; the user
should map them for IEC61850 communication using GR-TIEMS. Figure 4.2-55 illustrates
how to map a signal; it indicates that the signals for the DPSY01 function are required to be
mapped for IEC 61850 communications.
SBOw
Oper
Cancel
origin
stSeld
sboClass† (choice "operate-once")
ctlmodel (choice "SBOes or SBOns")
†"sboClass" can be found by scrolling down.
Oper
origin
ctlmodel (choice "DOes or DOns" )
- 602 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)