Operation time reset function (OPTIM)
As shown in Figure 4.4-1, all operation-times measured by the DPOS, DPSY, and TPOS
functions† can be cleared when the operation time reset controller (OPTIM) function issues a
reset command "OPTR01_RST_CMD". That is, within the respective functions the measured
time intervals (OT1 and the others‡) are entirely cleared upon occurrence of the reset command.
OPTIM function
Sending reset command
"OPTR01_RST_CMD"
"OPTR01_RST_CMD"
Figure 4.4-1 Reception of a reset command
†Note: For more information with regard to measurement, refer to the section
"Measurement of operation intervals" for the respective DPOS, DPSY, and TPOS
functions. The user should note that all interval OTs specific to a particular
function are cleared by the OPTIM reset command.
Sending reset command
"OPTR01_RST_CMD"
Sending reset
command
- 647 -
DPSY01 function
Clearing measured time-intervals
"OT1", "OT2", "OT3" and "OT4"
DPOS01 function
Clearing measured time-intervals
"OT1", "OT2", "OT3" and "OT4"
TPOS01 function
Clearing measured time-intervals
"OT1", "OT2", "OT3" and "OT4"
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)