"TPOS_Dev1-P3", respectively. The "TPOS_Dev1-All" represents the net counter
of "TPOS01_ST_P1", "TPOS01_ST_P2" and "TPOS01_ST_P3".
Receiving "change value for counter" from the remote-end
(i)
Mapping of Input point required
Figure 4.9-47 depicts the logic when a "change value for counter" command is received at the
TPOS01 function. With regard to the net counter, the input-point "DEV01_ALLCNT_REQ" is
used. With regard to a P1-control counter, the input-point "DEV01_P1CNT_REQ" is used. For
P2-control and P3-control, the input-points "DEV01_P2CNT_REQ" and "DEV01_P3CNT_REQ"
are used.
Input
Command "change value for counter"
513001_7004016D09
DEV01_ALLCNT_REQ
Figure 4.9-47 Change counter value in net counter
‡Note: The "operate condition" signal is provided from the operate condition logic shown
in Figure 4.9-49.
Note: The user can apply the other counter change commands for P1-control, P2-control
and P3-control as shown in Table 4.9-24. The resultant signals for the other
TPOS02-24 logics are shown in Table 4.9-23.
Output signal to BO
The TPOS01 function can issue a "Result" signal at output point "TPOS01_SLD_CSCN".
Receiving "change value for counter" from the local-end
(ii)
Input signal from the front panel
Figure 4.9-48 depicts the logic when a "change value for counter" command is provided in the
TPOS01 function. The command is provided from the sub-menu (see Figure 4.9-46).
Input
Command "Change value"
Figure 4.9-48 Changing value by the operation of the front panel in TPOS01
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
Operate Command
&
Operate condition‡
Operate logic in TPOS01
TPOS01 function (Function ID: 513001)
- 836 -
Output
"TPOS01_SLD_CSCN"
(513001 8A04011F8B)
by the remote-end in TPOS01
Output
"TPOS01_SLD_CSCN"
(513001 8A04011F8B)
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)