Toshiba GR200 Series Instruction Manual page 407

Hide thumbs Also See for GR200 Series:

Advertisement

VCHK1 setting for 1CB system
2.25.4
When the VCHK1 is applied to 1CB system, OVB and UVB check the voltage of a Bus-bar,
whereas OVL and UVL check the voltage of Line, as described earlier. The Bus-bar and Line
voltages are obtained in the VCT
[SYN-VLine] in accordance with the phase(s) of input-voltage(s). The following are the setting
examples when VCHK is used in 1CB system.
Note: For more information on VCT, see
1
module
Scheme switch
SYN-VBus
SYN-VLine
. Thus, user should set the scheme switches [SYN-VBus] and
1
. For external connection, see
Table 2.25-6 VCHK line selection setting
Set
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
V2-L1 / V2-L2 / V2-L3
V2-L12 / V2-L23 / V2-L31
V3 / V4
V-L1 / V-L2 / V-L3
V-L12 / V-L23 / V-L31
V2-L1 / V2-L2 / V2-L3
V2-L12 / V2-L23 / V2-L31
V3 / V4
- 386 -
Chapter Technical description: Transfer
Appendix: Typical external connection
Selection of Bus
voltage(Running Voltage) for
SYN1
Selection of Line voltage
(Incoming Voltage) for SYN1
6F2S1915 (0.46)
.
Comment
GRZ200 (Soft 031 & 032)