6F2S1915 (0.46)
Switch on to fault (SOTF-OC)
The switch-onto-fault function (SOTF-OC) is used to detect and rapidly clear faults when
circuit breakers (CBs) are closed onto a pre-existing fault in the protected zone. If a circuit
breaker is closed onto a permanent fault, the memory circuit in the IED will be unable to
memorize the voltage data required to retain the pre-fault values. This is because the voltage
input to distance measuring elements is absent continuously prior to and after the fault
particularly with voltage transformers installed on the line side; as a result, the fault cannot
be detected by conventional standard protection functions. Therefore, in order to avoid such
failures, SOTF-OC is applied so that the fault can be detected for a specific period following
the closure of the CB.
─────────────────────────────────────────────────────────────────
Note:
The implementation of particular features is dependent upon the selection of
hardware and the configuration of functions. Several IED models do not support certain
features. To determine whether a particular feature has been implemented within an IED,
identify the IED ordering number; and check the order number for the "G&T position" whilst
Appendix: Ordering
referring to the comparison table below. For more information, see
.
Table 2.2-1 Comparative table in respective ordering numbers
Ordering No. at "G&T"
Sec.
Feature
31
32
Main features
✓: Applicable
NA: Not applicable
GRZ200 (Soft 031 & 032)
- 117 -

Advertisement

loading