Setting
4.6.7
Synchronism (Function ID: 560001 )
Setting items
SYNC01_SYNCHK1EN
SYNC02_SYNCHK2EN
SYNC 01
SYNC01_TLRDIDRLI
SYNC01_TDRDI
SYNC01_TSYN
SYNC01_TSYN2
SYNC01_Split_EN
SYNC01_LRDIEN
SYNC01_DRLIEN
SYNC01_DRDIEN
SYNC 02
SYNC02_TLRDIDRLI
SYNC02_TDRDI
SYNC02_TSYN
SYNC02_TSYN2
SYNC02_Split_EN
SYNC02_LRDIEN
SYNC02_DRLIEN
SYNC02_DRDIEN
Range
Unit
Off / On
- SYNC DEV1 synchronism check switch
Off / On
- SYNC DEV2 synchronism check switch
V check timer(Live Run. & Dead Incom., Dead
0.00 - 5.00
s
Run. & Live Incom.)
0.00 - 5.00
s V check timer(Dead Run. & Dead Incom.)
0.00 - 100.00
s synchronism check timer(Loop)
30 - 1800
s Synchronism check time up
SYNC DEV1 split synchronism check mode
Off / On
-
enable
SYNC DEV1 Live Run. & Dead Incom. close
Off / On
-
mode enable
SYNC DEV1 Dead Run. & Live Incom. close
Off / On
-
mode enable
SYNC DEV1 Dead Run. & Dead Incom. close
Off / On
-
mode enable
V check timer(Live Run. & Dead Incom., Dead
0.00 - 5.00
s
Run. & Live Incom.)
0.00 - 5.00
s V check timer(Dead Run. & Dead Incom.)
0.00 - 100.00
s synchronism check timer(Loop)
30 - 1800
s Synchronism check time up
SYNC DEV2 split synchronism check mode
Off / On
-
enable
SYNC DEV2 Live Run. & Dead Incom. close
Off / On
-
mode enable
SYNC DEV2 Dead Run. & Live Incom. close
Off / On
-
mode enable
SYNC DEV2 Dead Run. & Dead Incom. close
Off / On
-
mode enable
- 696 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
Off
Off
5.00
5.00
10.00
60
Off
On
On
On
5.00
5.00
10.00
60
Off
On
On
On