Operate logic in TPOS01
"
"
TPOS01_P1EX_BO
(513001_8104011DD0)
Operate logic for
P1-control
in TPOS01
To contact health
check
"
"
TPOS01_P2EX_BO
(513001_8204011DD3)
Operate logic for
P2-control
in TPOS01
To contact health
check
"
"
TPOS01_P3EX_BO
(513001_8204011DD6)
Operate logic for
P3-control
in TPOS01
To contact health
check
Figure 4.9-58 Example of operate commands connected with BO4-BO2
†Note: Table 4.9-20 shows the remaining signals except for "TPOS01".
Contact health check
(iv)
The TPOS01 function has contact health check feature for the BO circuits; hence, the user is
able to connect an output signal to the contact health check function when Fixedlogic is set for
scheme switches [TPOS01- LGP1EXOT] to [TPOS01-LGP3EXOT]†. Consequently, the TPOS01
function can determine whether the signal has been successfully output from the BO. If a
failure is reported, the TPOS01 function determines that the signal is not output successfully
to the BO; then the command is canceled immediately and the TPOS01 function returns to the
"Wait for a command" stage.
†Note: Table 4.9-21 shows settings for the health check feature in the other TPOS
functions.
Setting for "select command P1/P2/P3"
For example, the point"TPOS01_P1SL_BO" is connected to the BO1 circuit for the issuing of
BO4–BO6 circuit at IO#1 (Function ID: 200B01)
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO4
200B01 310203E11D
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO5
200B01 310204E11D
Signal designated by
setting [Input signal 1]
[Input signal 2]
[Input signal 3]
[Input signal 4]
Connected by
"Programming"
[Input signal 5]
[Input signal 6]
[Input signal 7]
[Input signal 8]
PLC connection point in BO6
200B01 310205E11D
- 846 -
"
"
BO4
(200B01_8302031112)
≥1
DRIVER
&
≥1
On
[BO4_CPL]
&
(
200B01_8302031113)
Off
BO4_SOURCE
"
"
BO5
(
200B01_8402041112)
≥1
DRIVER
≥1
&
On
[BO5_CPL]
&
(
200B01_8402041113)
Off
BO5_SOURCE
"
"
BO6
(
200B01_8502051112)
≥1
DRIVER
≥1
&
On
&
[BO6_CPL]
(
200B01_8502051113)
Off
BO6_SOURCE
6F2S1915 (0.46)
Terminal and
wire
Operate
command
P1
BO4
"
"
BO4-RB
To contact health
check
Operate
command
P2
BO5
"
"
BO5-RB
To contact health
check
Operate
command
P3
BO6
"
"
BO6-RB
To contact health
check
GRZ200 (Soft 031 & 032)