Download Print this page

Toshiba GR200 Series Instruction Manual page 315

Hide thumbs Also See for GR200 Series:

Advertisement

Setting
2.18.5
OSTZ(Function ID: 478001)
Setting items
OSTZ-EN
OSTZ-R1
OSTZ-R2
OSTZ-XF
OSTZ-XB
TOSTZ1
TOSTZ2
OSTZ-Output
Range
Unit
1A rating
5A rating
Off / On
- OSTZ protection scheme switch
15.00 -
3.000 -
- OSTZ resistive reach (at Right side)
150.00
30.000
5.00 -
1.000 -
- OSTZ resistive reach (at Left side)
50.00
10.000
5.00 -
1.000 -
- OSTZ reactive reach (at Forward side)
250.00
50.000
1.00 -
0.200 -
- OSTZ reactive reach (at Backward side)
50.00
10.000
0.01 - 1.00
s OSTZ out-of-step timer
0.01 - 1.00
s OSTZ out-of-step timer
Trip / BO
- OSTZ trip signal output position
- 294 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
Off
25.50
5.100
12.50
2.500
30.00
6.000
5.00
1.000
0.04
0.04
Trip

Advertisement

loading

This manual is also suitable for:

Grz200