Mapping for IEC61850 communication
4.11.6
The user can operate the ASEQ function using IEC 61850 communications after first
completing the appropriate mapping using the GR-TIEMS software. Note that the ASEQ01
function is designed for the "Single Point Controller (SPC) class" described in the IEC 61850
communications standard. The user should follow steps:
Step1: Editing Logical Node
Step2: Mapping output data
Step3: Mapping input data
Editing Logical Node
(i)
The user should implement a logical node (LN) for the ASEQ01 function. Figure 4.11-5
exemplifies LN editing; the LN "(GAPC1)" is chosen for the ASEQ01 function. After the user
has defined an object "SPCSO1", the ASEQ01 logical node is saved with the name "SPCSO1"
plus "LN Instance". A definition for the object "SPCSO1" is made in the ASEQ01 logical node.
Choose either the SBO mode or the DIR mode when editing the LN.
Figure 4.11-5 Defining "SPCSO1" object in GAPC1 logic node
Defining SBO mode
Figure 4.11-6 exemplifies the settings in LN "GAPC1" when the SBO mode is required for the
ASEQ01 function. In SBO control, the user should select the following items for the object
reference "GAPC1$SPCSO1" using the GR-TIEMS software;
SBO defined in LN
- 880 -
6F2S1915 (0.46)