Multi-level overcurrent elements (OCMFS)
2.20.4
Characteristic of OCMFS
(i)
A current fluctuates when there is a condition about out of step, so the function of multi-level
overcurrent elements (OCMFS) is provided in the FS function. That function includes seven
detectors placed at seven multiple levels.
Figure 2.20-2 illustrates that that OCMFS includes those current level detectors (LDs).
Table 2.20-2 shows a detector threshold between operating and resetting is fixed in each LD.
LD element starts operating if the current exceeds its operating threshold, and the LD will
reset its operation when the current is below 80% of the operating threshold.
LD2
LD1
0
Figure 2.20-2 OCMF characteristics
- 301 -
LD7
LD6
LD5
LD4
LD3
I
D.O./P.U.=0.8
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)