Monitoring jacks
5.6.4
A monitoring jack including a LED is provided so that the user can monitor a binary signal on
the logic straightforwardly. For example, when the user wishes to monitor the operating state
of a relay function, set the signal number (Data ID) that the user wishes to monitor; then the
user can see lighting the LED when the relay is operated. Using with an oscilloscope, the user
can also observe the binary signal that comes from the monitoring jack; three monitoring jacks
(Term A, B, and C) are available on the front panel.
Table 5.6-9 Output terminals for signal monitoring (No default setting)
Jack
Jack name
A
Term A
B
Term B
C
Term C
When the user wishes to test the phase-A element the OC1 relay using an oscilloscope,
for example, set the phase-A monitoring point (44001 8000011C20†) for the setting [Term A],
as shown in Figure 5.6-5. Consequently, the OC1 operating signal is outputted to the jack at
the Term A. The LED at the Term A is also lit in step with the output signal. The user can use
to monitor the phase-B and phase-C signals using by settings respective Data IDs for the [Term
B] and [Term C]. We shall see the menus for the Term A to Term C in Chapter
Test sub-menu: Signal monitoring screen.
OC function
(Function ID: 440001)
440001 8000011C20
A
OC1
440001 8100011C21
B
440001 8200011C22
C
†Note: The monitoring point is just selected for the explanation; the user can select a
monitoring point from the relay applications and the control and monitoring
applications. The monitoring points is listed as PLC monitoring points in each
function.
LED Color
Yellow
Yellow
Yellow
Monitoring jack (Function ID: 201301)
Signal designated by
setting [Term A]
Signal designated by
setting [Term B]
Signal designated by
setting [Term C]
Figure 5.6-5 Monitoring logics A, B and C
- 972 -
Remarks
Set user's preferred signal number
Set user's preferred signal number
Set user's preferred signal number
Jacks and LEDs
Term
DRIVER
A
"TEST-A"
(
201B01_3100221001)
Term
DRIVER
B
"TEST-B"
(
201B01_3100231001)
Term
DRIVER
C
"TEST-C"
(
201B01_3100241001)
GRZ200 (Soft 031 & 032)
6F2S1915 (0.46)
User interface:
Signal to the
oscilloscope
Term A LED
Signal to the
oscilloscope
Term B LED
Signal to the
oscilloscope
Term C LED