Mapping for IEC 61850 communication
4.5.3
The user can operate the TTIM01 function using IEC 61850 communications after first
mapping the function using GR-TIEMS. The user should proceed as follows
Step1:
Editing Logical Node
Step2:
Mapping output data
Step3:
Mapping input data
Editing Logical Node
(i)
The user must make a logical node (LN) for the TTIM01 function. Figure 4.5-3 exemplifies LN
editing; LN "GGIO1301" is selected for the TTIM01 function for IEC 61850 communication.
After the user has defined an object "ISCSO1", the TTIM01 logical node can be saved with the
name "GGIO1301". Define the object "ISCSO1" in the TTIM01 logical node. Either the SBO
mode or the DIR mode can be chosen when editing the LN.
Figure 4.5-3 Defining "ISCSO1" object in GGIO1301 logic node
Defining SBO mode
Figure 4.5-4 exemplifies the settings in LN "GGIO1301" when the SBO mode is required for
the TTIM01 function. For SBO control, the user should select the following items for the
"GGIO1301$ISCSO1" using GR-TIEMS;
SBO defined in LN
- 665 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)