Scheme logic and setting
2.18.4
Figure 2.18-5 shows the scheme logic of the OSTZ function. When the condition of out-of-step
is yielded, the OSTZ function can detect the motion of the loci impedance from Zone A, Zone B
to Zone C
. Then the OSTZ function will issue a trip command when the locus enters to Zone
1
C and when the locus keeps staying in Zone C for setting times [TOSTZ1] and [TOSTZ2].
The user should set scheme switch [OSTZ-EN] On in order to operate the OSTZ function.
The user should set scheme switch [OSTZ-Output] Trip to issue a trip command for the trip
circuit (TRC
). When the user requires outputting the trip command for the binary output
2
circuit (BO
) instead of the TRC, the user should set BO the scheme switch [OSTZ-Output].
3
PLC connection point "OSTZ-BLOCK" is used to blocking the OSTZ function by an
external signal. The PLC function
Note: The OSTZ function also issues a trip command when the motion of the locus from
1
Zone C to Zone B, Zone A.
Note: Trip circuit is discussed separately. See Chapter
2
function
Note: Binary output circuit is furnished on Binary IO module. See Chapter
3
description: Binary IO module: Binary output circuit
Note: For more information, see Chapter
4
makes possible the connection with the logic.
4
.
- 292 -
Relay application: Trip circuit
.
PLC function
.