4.4.2
In the SBO control mode the reception of the cancel command is possible when the cancel
conditions are satisfied. Accordingly, the function can discard the select command; finally, the
operation returns to the initial stage (i.e., "Wait for a command".)
Receiving "Cancel" from the remote-end
(i)
Figure 4.4-7 outlines the reception of the cancel command from the remote end.
Wait for a command
Select logic
Command Reset from the
remote-end
Figure 4.4-7 Outline of cancel command from the remote-end
Input point required mapping
(ii)
Figure 4.4-8 shows the cancel logic when a "Cancel command (Remote-Cancel)" signal enters
the OPTIM function. The input-point "OPTR01_CONTROL_REQ" is the same point of the
Figure 4.4-5.
Input
Command "Cancel"
529001 700C016D08
OPTR01_CONTROL_REQ
†Note: The criteria "unmatched conditions" are determined when "Test-bit status" in a
command is not identical to "IED test status".
Wait for a next command
Cancel by the remote-end
Signal reception in
IEC61850
Operate logic
Operate command
Operate logic
OPTIM function (Function ID: 529001)
Cancel command
Unmatched condition
detected†
Figure 4.4-8 Cancel from the remote-end
- 652 -
Cancel
Cancel logic
decision
510001 7001016D08
Cancel logic in OPTR
&
&
6F2S1915 (0.46)
Success
Do nothing
Failed
Output
To "Wait for a command"
Successes to cancel
"Do nothing"
Operation Failed
GRZ200 (Soft 031 & 032)