Download Print this page

Toshiba GR200 Series Instruction Manual page 192

Hide thumbs Also See for GR200 Series:

Advertisement

OC (Function ID: 440001)
Setting items
OC4-Rtimer
TOC4R
OC4-RTMS-US
ORG
OC4
OC4-DPR
OC4-TMS-ORG
OC4-Rtimer
TOC4R
OC4-RTMS-
ORG
OC4-k
OC4-a
OC4-c
OC4-kr
OC4-b
Output
OC4-2fBlk
OC4-VTFBlk
OC4-OPMD
OC4-UseFor
OC4-ARCBlk
Range
Unit
1A rating
5A rating
DEF / DEP
- OC4 reset delay type of US
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 -
0.10 -
A OC4 threshold (in IDMT mode)
5.00
25.00
10 - 100
% OC4 drop-out/pick-up ratio
0.010 - 50.000
- OC4 time multiplier of ORG inverse curve
DEF / DEP
- OC4 reset delay type of US
0.00 - 300.00
s OC4 definite time reset delay
OC4 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
0.00000 - 500.00000
- OC4 user original curve coefficient
0.00000 - 10.00000
- OC4 user original curve coefficient
Non / Block-3P /
- OC4 operation block by 2f-detection
Block-PerP
Non / Block
- OC4 operation block by VTF
3POR / 2OUTOF3
- OC4 operation mode
Trip / Alarm
- OC4 used for trip or alarm
Non / Block
- Autoreclose block by OC4
- 171 -
6F2S1915 (0.46)
Contents
GRZ200 (Soft 031 & 032)
Default
Note
1A
5A
DEF
0.00
1.000
1.00
5.00
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
Non
3POR
Trip
Block

Advertisement

loading

This manual is also suitable for:

Grz200