Download Print this page

Toshiba GR200 Series Instruction Manual page 889

Hide thumbs Also See for GR200 Series:

Advertisement

Mapping for IEC61850 communication
4.10.2
Sending a report to the client is possible after the mapping is performed for IEC 61850
communication using GR-TIEMS. The user should proceed as follows,
Step1:
Step2:
Editing Logical Node
(i)
The user must make a logical node (LN) for the GENBI function. Figure 4.10-4 exemplifies LN
making; LN "GGIO101" is selected for the GENBI function. After editing, the GENBI logical
node can be saved with the name "GGIO101". Object "Ind1" is defined in the GENBI function.
Figure 4.10-4 Defining "Ind1" object in GGIO101 logic node
Mapping output data
(ii)
With the IEC 61850 communications standard a GOOSE message can be used to send a signal
to a client. The user will need to collect the signals corresponding to the GENBI function and
then map them for IEC 61850 communication using GR-TIEMS.
Table 4.10-5 shows the mapping signals that are required within the GENBI function for
IEC 61850 communications. Figure 4.10-5 shows how to map a signal.
Table 4.10-5 Mapping signals for Ind1 object in GENBI function
Object_reference
Ctrl/GGIO101$Ind1
Ctrl/GGIO101$Ind1
Ctrl/GGIO101$Ind1
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850 standard.
Editing Logical Node
Mapping output data
Attribute
Type
stVal
BOOLEAN
q
Quality
t
Timestamp
- 868 -
FC
Signal Number
ST
580001 0010001001
ST
580001 3110001005
ST
580001 9010001006
6F2S1915 (0.46)
Signal Name
SLOT1 GBI01_STATE
SLOT1 GBI01_QUALITY
SLOT1 GBI01_TIMESTAM
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200