Hybrid Cable Shield Grounding Connection - Samsung Smart MBS RRH-P4 Installation Manual

Table of Contents

Advertisement

2600-00CTEIGAA
Ver.

2.8.5 Hybrid Cable Shield Grounding Connection

Follow the steps below to connect the shield ground cable of hybrid cable to the ground bar
in the DU cabinet.
1) Install the shield ground cable of hybrid cable to the ground bar on the left of the DU cabinet.
2) Remove the M6 Hex. nuts and lock washers installed in the ground bar.
3) Align the pressure terminal assembled on the cable to the insert bolt of the ground bar, and fasten it
using the removed M6 Hex. nut and lock washer.
Figure 2.43 Hybrid Cable Shield Grounding Connection_DU Cabinet
© SAMSUNG Electronics Co., Ltd.
4.0
Shield Ground Cable of Hybrid Cable
Smart MBS RRH-P4 Installation Manual/Ver.3.0
Ground Bar (in DU Cabinet)
Pressure Terminal
M6 Lock Washer
M6 Hex. Nut
Shield Ground Cable of Hybrid Cable #2
Shield Ground Cable of Hybrid Cable #1
Shield Ground Cable of Hybrid Cable #0
2-63