Transferring To Bypass Mode Manually; Setting The S-Eco Mode - Huawei UPS5000-H User Manual

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)

7.4 Transferring to Bypass Mode Manually

Before you shut down the inverter, ensure that the bypass is normal. If the bypass
is abnormal, after you shut down the inverter, the UPS supplies no power, and the
loads are powered off.
Shut down the inverter on the LCD or WebUI. The UPS automatically transfers to
bypass mode.

7.5 Setting the S-ECO Mode

Prerequisites
Context
Issue 05 (2021-10-13)
NO TICE
NO TE
If you shut down the inverter when the bypass input voltage or frequency exceeds the
specified threshold, the UPS supplies no power, and the loads are powered off.
Only the three-phase four-wire 380 V AC/400 V AC/415 V AC (line voltage)
model supports the S-ECO mode.
The system is working in inverter mode.
By default, the system works in a mode other than S-ECO. To enable the
system to work in S-ECO mode, set the working mode to S-ECO mode.
In S-ECO mode, the bypass takes priority over the inverter in supplying power.
If the bypass fails, the UPS transfers to inverter mode.
Both a single UPS and a parallel system support S-ECO mode which ensures
higher efficiency.
To avoid frequent transfers between S-ECO mode and normal mode, do not
set S-ECO mode when the bypass input is unstable or is sensitive to load
changes.
When the load is less than 5%, the S-ECO mode does not present obvious
advantages so the S-ECO mode is not recommended.
Before setting S-ECO mode, ensure that the bypass is working properly.
In S-ECO mode, the UPS automatically selects the VFD, VI, or VFI working
mode in real time based on the combination of physical parameters such as
the load rate, load current THDi, load power factor, and real-time input
voltage waveform.
S-ECO mode VFI: When the input voltage is of poor quality and fluctuates
greatly (the voltage and frequency exceed the specifications, the PF is less
than 0.5, or the load rate is less than 5%), the UPS automatically transfers to
normal mode to avoid supplying power of poor waveforms to loads. The UPS
monitors the input voltage waveform in real time. When the input voltage
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
336

Advertisement

Table of Contents
loading

Table of Contents