Bypass Input Electrical Specifications; Battery Electrical Specifications - Huawei UPS5000-H User Manual

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Item
Harmonic current

11.5 Bypass Input Electrical Specifications

Table 11-6 Bypass input electrical specifications
Item
Power system
Rated voltage
Rated frequency
Frequency range
Input mode

11.6 Battery Electrical Specifications

The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Issue 05 (2021-10-13)
Specifications
● THDi < 9% (30% linear load), THDi < 6% (50% linear load),
THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear
load), THDi < 5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
Specifications
Three-phase four-wire + PE/Three-phase three-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz
by default)
The mains input and bypass input share a power source (by
default) or use different power sources.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
SmartLi
376