UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Item
Harmonic current
11.5 Bypass Input Electrical Specifications
Table 11-6 Bypass input electrical specifications
Item
Power system
Rated voltage
Rated frequency
Frequency range
Input mode
11.6 Battery Electrical Specifications
The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Issue 05 (2021-10-13)
Specifications
● THDi < 9% (30% linear load), THDi < 6% (50% linear load),
THDi < 3% (100% linear load)
● THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear
load), THDi < 5% (100% non-linear load)
Remarks:
1. The preceding specifications are met when the mains input
and bypass input share a power source.
2. The input THDu is less than 2%.
Specifications
Three-phase four-wire + PE/Three-phase three-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
50 Hz/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz
by default)
The mains input and bypass input share a power source (by
default) or use different power sources.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
11 Technical Specifications
SmartLi
376