UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
EMC Test Item
ESD immunity
Conducted susceptibility
Radiated susceptibility
Electrical fast transient
Surge
Impact current (lightning protection)
Voltage dips and short interruptions (220 V AC)
Power frequency magnetic field

11.4 Mains Input Electrical Specifications

Table 11-5 Mains input electrical specifications
Item
Power system
Rated voltage
Voltage range
Rated frequency
Frequency range
Power factor
Issue 05 (2021-10-13)
Specifications
Three-phase four-wire + PE/Three-phase three-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
0–30°C: not derated at 323–485 V AC, derated from 100% load to
45% load at 323–191 V AC, and derated from 45% load to 35%
load at 191–138 V AC
30–40°C: not derated at 342–485 V AC, derated from 100% load to
45% load at 342–191 V AC, and derated from 45% load to 35%
load at 191–138 V AC
50 Hz/60 Hz
40–70 Hz
● > 0.99 (100% load)
● > 0.98 (50% load)
● > 0.94 (30% load)
Copyright © Huawei Technologies Co., Ltd.
Standard
IEC 61000-4-2
EN/IEC 62040-2
EN/IEC 61000-4-6
EN/IEC 62040-2
EN/IEC 61000-4-3
EN/IEC 62040-2
IEC 61000-4-4
EN/IEC 62040-2
IEC 61000-4-5
If a surge protection box is configured: 5 kA
(common mode), criterion B
IEC 61000-4-11
IEC 61000-4-8