Figure 7-27 S-ECO system status (VFD)
Figure 7-28 S-ECO system status (VI)
----End
7.11 Transferring a UPS to Bypass Mode Manually
Before you shut down the inverter, ensure that the bypass is normal. If the bypass
is abnormal, after you shut down the inverter, the UPS supplies no power, and the
loads are powered off.
Shut down the inverter on the LCD or WebUI. The UPS automatically transfers to
bypass mode.
Issue 02 (2022-07-18)
NO TICE
NO TE
If you shut down the inverter when the bypass input voltage or frequency exceeds the
specified threshold, the UPS supplies no power, and the loads are powered off.