UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Item
Voltage
Frequency
Voltage distortion
Power factor
Transfer time
(normal)
Output voltage
imbalance
Inverter overload
capability
Inverter output short-
circuit capability
Issue 05 (2021-10-13)
1200 kVA
380 V AC/400 V AC/415 V AC (line voltage)
● In normal mode, the frequency is synchronous with the bypass input
frequency.
● In battery mode, the frequency is 50 Hz/60 Hz with a tolerance of
±0.05%.
● Linear load THD < 1% (50–100% load balancing)
● Non-linear load THD < 3% (50–100% load balancing)
1
● Double conversion mode: uninterrupted transfer 0 ms; interrupted
transfer ≤ 5 ms
● S-ECO mode: 0 ms (supported only by the three-phase four-wire
model)
Voltage imbalance: ±1%
Phase imbalance: 120±1°
Inverter overload capability for front-to-back airflow:
● 105% < load ≤ 110%: transfers to bypass mode after 60 min or longer
(ambient temperature ≤ 30°C)
● 100% < load ≤ 110%: transfers to bypass mode after 60 min or longer
(ambient temperature > 30°C)
● 110% < load ≤ 125%: transfers to bypass mode after 10 minutes or
longer
● 125% < load ≤ 150%: transfers to bypass mode after 1 minute or
longer
● Load > 150%: transfers to bypass mode after 200 ms or more;
withstands at least 50 shocks
Inverter overload capability for top airflow:
● 100% < load ≤ 110%: transfers to bypass mode after 60 minutes or
longer
● 110% < load ≤ 125%: transfers to bypass mode after 10 minutes or
longer (ambient temperature ≤ 30°C)
● 110% < load ≤ 125%: transfers to bypass mode after 1 minute or
longer (ambient temperature > 30°C)
● 125% < load ≤ 150%: transfers to bypass mode after 1 minute or
longer (ambient temperature ≤ 30°C)
● 125% < load ≤ 150%: transfers to bypass mode after 20 seconds or
more (ambient temperature > 30°C)
● Load > 150%: transfers to bypass mode after 200 ms or more;
withstands at least 50 shocks
If the initial load rate is less than 40%, twice the rated current can be
tolerated for 300 ms in the case of inverter output short-circuit.