100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Item
Battery
Nominal battery
input
discharge current
(SmartLi)
(A)
Maximum battery
discharge current
(A)
Recommended
cross-sectional
area
Equipotentia
Recommended
l ground
cross-sectional
point
area (mm
Issue 05 (2021-10-13)
1300 kVA
2701
3390
For details, see the IEC-60364-5-52 specifications and
SmartLi User Manual .
16
2
)
The currents listed in the table are measured at a rated voltage of 380 V.
When selecting, connecting, and routing power cables, follow local safety
regulations and rules.
When the external conditions such as the cable layout or ambient
temperatures change, perform verification in accordance with the
IEC-60364-5-52 or local regulations.
If the rated voltage is 400 V, multiply the currents by 0.95; if the rated voltage
is 415 V, multiply the currents by 0.92.
When the primary loads are non-linear loads, increase the cross-sectional
areas of the neutral wires by 1.5–1.7 times.
The nominal battery discharge current refers to the current of forty 12 V
batteries at 480 V in standard configuration.
The maximum battery discharge current refers to the current when forty 12 V
batteries in standard configuration, that is, two hundred and forty 2 V battery
cells (1.67 V/cell), stop discharging.
The battery cable specifications are selected based on 40 batteries by default
and compatible with application scenarios with 30–50 batteries.
When the mains input and bypass input share a power source, configure
mains input power cables as input power cables. In addition, cables
recommended in the table apply only when the following requirements are
met:
Routing mode: The cables are routed over a tray or bracket in a single
layer (E in IEC 60364-5-52). The distance between cables should be
greater than twice the cable diameter. Routing mode: The cables are
routed over a tray or bracket in a single layer (E multi-core and G single-
core in IEC 60364-5-52).
The ambient temperature is 30°C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than
1%.
Conductor insulation: PVC insulation
Copyright © Huawei Technologies Co., Ltd.
1400 kVA
1500 kVA
2909
3117
3650
3911
6 Installation
1600 kVA
3324
4172
101