Huawei UPS5000-H User Manual page 339

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 7-1 Settings Wizard - Language
(1) Lead-acid battery scenario
Step 2 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Issue 05 (2021-10-13)
NO TE
● Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair, affecting the normal operation.
● After network parameters are set, connect the UPS to the network, ensuring that
maintenance personnel can manage or control the UPS remotely. If you do not need
remote management, retain the default network parameter settings.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
(2) Lithium battery scenario
329

Advertisement

Table of Contents
loading

Table of Contents