UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 6-103 Installing equipotential ground cable for cabinets
Step 2 Install power cables between the UPS and the inductor cabinet.
● Cables have been preinstalled and bound in the inductor cabinet.
● The cables from the inductor cabinet to the UPS are configured based on the
● Cables must be bound to the nearest beam or cable bridge according to the
Issue 05 (2021-10-13)
NO TICE
longest cable length before delivery. If shorter cables are needed in the actual
installation scenario, you can cut the excess cables and crimp terminals.
route shown in the figure.
One power source
Figure 6-104 Removing the cover