Huawei UPS5000-H User Manual page 338

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Set system parameters with caution because the settings determine whether the
UPS can operate normally.
● Set Single/Parallel after double check. Incorrect settings may affect the normal
● Output voltage level refers to the line voltage level. Set it based on site
● Set Output frequency correctly. Otherwise, loads may be affected and the UPS
● Set all battery parameters correctly based on site requirements. Battery
Issue 05 (2021-10-13)
NO TICE
UPS operation.
requirements.
may not work properly.
parameter settings are critical to battery maintenance, battery lifespan, and
UPS discharge time.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
328