UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 6-401 Power supply to the top air-flow cabinet
----End

6.6.5 Installation in Top Cabling + Top Air-Flow Configuration

6.6.5.1 Installing Cabinets

Install cabinets by referring to Single UPS Installation (1600 kVA, Three-Phase
Three-Wire) > Installation in Top Air-Flow Configuration > Installing Cabinets.

6.6.5.2 Installing Rectifiers in the Inductor Cabinet

Context
Rectifiers are delivered separately, and baffle plates are placed in the fitting bag of
the inductor cabinet.
Procedure
Step 1 Install the rectifiers and baffle plates.
1.
2.
3.
4.
5.
6.
Issue 05 (2021-10-13)
If both the top cabling component and the top air-flow cabinet are
configured, cabinets can be installed against a wall and cables can be routed
from the top.
The following procedure applies to installation against a wall. If cabinets are
not installed against a wall and there is operation space at the rear of the
cabinets, you need to install the cabinet combination screws at the rear and
the anchor screws at the bottom.
Push the locking latch leftwards.
Pull out the handle.
Insert the rectifier into the slot and push it along the guide rails until it is in
position.
Push the handle in place and lock it.
Push the locking latch rightwards to secure the handle.
Install baffle plates for the vacant slots.