Lead-Acid Battery Test; Performing A Forced Equalized Charging Test - Huawei UPS5000-H User Manual

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)

7.7.1 Lead-Acid Battery Test

7.7.1.1 Performing a Forced Equalized Charging Test

Context
This item allows you to perform equalized charging on batteries forcibly.
Before performing a forced equalized charging test, ensure that:
● The mains input is normal.
● Batteries are properly connected.
● Batteries are not in equalized charging mode.
Procedure
Step 1 On the home screen of the LCD, choose System Info > Maintenance > Battery
Maint.
Step 2 Tap Start on the right of Forced Equalized Charging to start a forced equalized
charging test.
Figure 7-14 Starting a forced equalized charging test
----End
Issue 05 (2021-10-13)
NO TICE
NO TE
The forced equalized charging test automatically stops in any of the following cases:
● The test duration reaches the forced equalized charging protection time (12–24 h, 18 h
by default).
● The UPS generates a battery overtemperature, overvoltage, or overcurrent alarm.
● An alarm is generated.
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
341

Advertisement

Table of Contents
loading

Table of Contents