Huawei UPS5000-H User Manual page 325

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 6-405 Conceptual diagram of a 1+1 parallel system
For a three-phase three-wire parallel system, connect cables according to the
preceding conceptual diagram. In addition, connect the mains input neutral wire
of each UPS together using a single 185 mm
Figure 6-406 Neutral cable connection for a three-phase three-wire parallel
system (using the 1200 kVA model top cabling configuration as an example)
A dual-bus parallel system consisting of two parallel subsystems is used as an
example.
Issue 05 (2021-10-13)
NO TE
A parallel system where three-phase three-wire input and output cables are connected
using a busway is not supported currently.
Copyright © Huawei Technologies Co., Ltd.
2
90°C-resistant copper flexible cable.