Huawei UPS5000-H User Manual page 128

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Figure 6-53 Installing covers
Step 7 Install the front and rear mounting plates.
Figure 6-54 Installing mounting plates
Step 8 Install a signal cable.
Issue 05 (2021-10-13)
NO TE
Separate the mains input cables, bypass input cables, and output cables by using top
beams.
If you need to log in to the WebUI of the UPS monitoring system, connect the
network port on a PC to the FE port on the monitoring interface card.
If the UPS needs to connect to an external network management device,
connect the external network management device to the RS485 port on the
monitoring interface card.
(Connection required only for SmartLi 2.0) If the UPS needs to connect to the
SmartLi, connect the COM port on the monitoring interface unit in the master
SmartLi cabinet to the COM2 port on the monitoring interface card.
Copyright © Huawei Technologies Co., Ltd.
6 Installation
118

Advertisement