Transferring To Maintenance Bypass Mode; Transferring From Maintenance Bypass Mode To Inverter Mode - Huawei UPS5000-H User Manual

100 kva power modules
Hide thumbs Also See for UPS5000-H:
Table of Contents

Advertisement

UPS5000-H-(1200 kVA-1600 kVA)
User Manual (100 kVA Power Modules)
Step 2 Choose logs that have been queried from the Log drop-down list box, and click
Export.
----End

7.8 Transferring to Maintenance Bypass Mode

● You are advised to install a lock on the maintenance bypass switch.
● Strictly observe the following procedure to transfer the UPS to maintenance
● In maintenance bypass mode, the mains supplies power to the loads directly
Step 1 Ensure that the status signal cable of the maintenance bypass switch for external
power distribution is connected to MT/0V. Choose System Info > Settings > Dry
Contact Set and set PDC maintenance breaker [MT] to Enable.
Figure 7-21 Maintenance bypass signal port (MT)
Step 2 Shut down the inverter. Choose Common Functions > Inv. OFF. After the inverter
shuts down, the UPS transfers to bypass mode, and the Bypass mode alarm is
displayed on the LCD.
Step 3 Turn on the maintenance bypass switch for external power distribution. Then, the
Maint. breaker closed and Bypass mode alarms are displayed on the LCD.
----End
7.9 Transferring from Maintenance Bypass Mode to
Inverter Mode
Before you transfer the UPS from the bypass mode to inverter mode, ensure that
the bypass input is normal.
Issue 05 (2021-10-13)
NO TICE
bypass mode. Otherwise, loads may power off.
over the maintenance bypass. If the mains is abnormal, the loads may power
off.
NO TICE
Copyright © Huawei Technologies Co., Ltd.
7 Single UPS Commissioning
348