NetCol5000-C(030, 032, 065) In-row Chilled Water
Smart Cooling Product
User Manual
4.1.2.3 (Optional) Humidifier Water Inlet Pipe
Figure 4-6 Connecting a humidifier water inlet pipe
(1) Connector with outer screw
threads: G 3/4 inch
4.1.2.4 Chilled Water Inlet and Outlet Pipes
The following illustrates how to connect water inlet and outlet pipes to reserved
ports on the cabinet.
Issue 06 (2022-12-15)
NO TE
The object shown in the dotted line box is the water inlet pipe connector with outer screw
threads delivered with smart cooling products. Other parts are not provided and need to be
purchased.
Copyright © Huawei Digital Power Technologies Co., Ltd.
(2) Adapter with inner screw
threads: G 3/4 inch. Plastic
materials such as PA66 and
metal materials are
recommended.
4 Installation
(3) Matched with the adapter,
the pressure resistance should
be at least 0.7 MPa
44