R410A Refrigerant - Huawei FusionCol8000-E240 User Manual

Modular indirect evaporative cooling system
Hide thumbs Also See for FusionCol8000-E240:
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Step 13 Choose Maint > Diagnostic > Enter to check the system pressure and
temperature and ensure the refrigerant is charged with an optimal status. Ensure
that the system is running normally without alarms.
Step 14 Install the adjustable side panel.
Step 15 Choose Maint > Performance Maint on the home screen to access the
performance maintenance screen, and clear the runtime of the compressor.
----End

8.4.13.2 R410A Refrigerant

Do not use refrigerant of poor quality. Huawei will not be liable for any device
damage caused by using refrigerant of poor quality.
Verify that the refrigerant is authentic in the following ways:
1.
2.
Figure 8-22 Refrigerant detection
Table 8-6 Mapping between temperatures and R410A saturation pressures
Temperatur
e (ºC)
0
Issue 01 (2021-01-30)
CA UTION
Dial the refrigerant vendor's hotline to confirm the refrigerant authenticity.
As shown in
Figure
8-22, place the refrigerant in an indoor place with
constant temperature and humidity for 24 hours. Then, use a thermometer to
measure the temperature of the refrigerant tank outer surface and connect a
pressure gauge to the pressure tank to measure the internal pressure. Find the
saturation pressure corresponding to the measured outer surface temperature
from
Table
8-6. If the deviation between the saturation pressure and the
measured internal pressure is greater than 0.2 MPa, the refrigerant does not
meet the requirements and needs to be replaced.
Saturation
Pressure –
Gauge
Pressure
(MPa)
0.7
Copyright © Huawei Technologies Co., Ltd.
Temperatu
Saturation
re (ºC)
Pressure –
Gauge
Pressure
(MPa)
19
1.31
8 System Maintenance
Temperatu
Saturatio
re (ºC)
n
Pressure –
Gauge
Pressure
(MPa)
38
2.21
161