Abbreviation
rE7
Name
File quantity error
• A parameter copy was attempted to the USB memory device in which the copy files from 001 to 099 had
Description
already been saved.
Check point
• Check if the number of copy files in the USB memory device has reached 99.
Corrective action
• Delete the copy file in the USB memory device and perform parameter copy again.
Abbreviation
rE8
Name
No PLC function project file
Description
The specified PLC function project file does not exist in the USB memory device.
• Check that the file exists in the USB memory device.
Check point
• Check that the folder name and the file name in the USB memory device is correct.
Corrective action
The data in the USB memory device may be damaged.
Abbreviation
Err.
Name
RES signal ON or communication circuit fault
• The RES signal is turned ON.
• The operation panel and inverter cannot make normal communication (contact faults of the connector).
Description
• This error may occur when the voltage at the input side of the inverter drops.
• When using a separate power source for the control circuit power (R1/L11, S1/L21) from the main circuit
power (R/L1, S/L2, T/L3), this error may appear at turning ON of the main circuit. It is not a fault.
• Turn OFF the RES signal.
Corrective action
• Check the connection between the operation panel and the inverter.
• Check the voltage on the input side of the inverter.
Causes and corrective actions