Mitsubishi Electric 800 Series Instruction Manual page 367

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(M) Monitor display and monitor output signal
Energy saving monitor list
• The items that can be monitored on the power saving monitor (Pr.52, Pr.54, Pr.158, Pr.774 to Pr.776 = "50") are indicated
below. (Only [1 Power saving] and [3 Average power saving] can be set to Pr.54 (terminal FM) and Pr.158 (terminal AM).)
Energy saving
monitored item
1
Power saving
2
Power saving rate
Average power
3
saving
Average power
4
saving rate
Average power cost
5
savings
• The items that can be monitored on the cumulative energy saving monitor (Pr.52, Pr.774 to Pr.776 = "51") are indicated
below.
(The monitor value of the cumulative monitor can be shifted to the right with Pr.891 Cumulative power monitor digit
shifted times.)
Energy saving
monitored item
Power saving
6
amount
7
Power cost saving
Annual power
8
saving amount
Annual power cost
9
savings

For communication, (RS-485 communication, communication option), the display increments are 1. For example, "10.00 kWh" is displayed as
"10" for communication data.

When using the LCD operation panel or the parameter unit, "kW" is displayed

The increment differs according to capacities. (FR-A860-01080 or lower / FR-A860-01440 or higher.)
NOTE
• The operation panel and the parameter unit have a 5-digit display. This means, for example, that when a monitor value in
0.01 units exceeds "999.99", the decimal place is moved up as in "1000.0" and the display changes to 0.1 units. The
maximum display number is "99999".
• The maximum value for communication (RS-485 communication, communication option) when Pr.898 Power saving
cumulative monitor clear = "9999" is "65535". The maximum value for the 0.01-unit monitor is "655.35", and the maximum
value for the 0.1-unit monitor is "6553.5".
366
PARAMETERS
Description and formula
The difference between the estimated value of the
required power during commercial power supply
operation and the input power calculated with the inverter.
Power supply during commercial power supply
operation - input power monitor
The power saving ratio with the commercial power
supply operation as 100%.
[1 Power saving]
Power during commercial power supply operation
The power saving ratio with Pr.893 as 100%.
[2 Power saving]
 100
Pr.893
The average power saving per hour during a
predetermined time (Pr.897).
∑ ([1 Power saving]  ∆t)
Pr.897
The average power saving ratio with the
commercial power supply operation as 100%.
∑ ([2 Power saving rate]  ∆t)
Pr.897
The average power saving ratio with Pr.893 as 100%.
[3 Average power saving]
 100
Pr.893
The average power saving in terms of cost.
[3 Average power saving]  Pr.896
Description and formula
The cumulative power saving is added up per hour.
∑([1 Power saving]  ∆t)
The power saving amount in terms of cost.
[6 Power saving amount]  Pr.896
Estimated value of annual power saving amount.
[6 Power saving amount]
Operation time during power saving accumulation
Pr.899
24  365 
100
Annual power saving amount in terms of cost.
[8 Annual power saving amount]  Pr.896
Increment
0.01 kW/
0.1 kW
 100
0.1%
0.01 kWh/
0.1 kWh
 100
0.1%
0.01/0.1
Increment
0.01 kWh/
0.1 kWh

0.01/0.1
0.01 kWh/

0.1 kWh

0.01/0.1
Parameter setting
Pr.895 Pr.896 Pr.897 Pr.899
9999

9999
0
1
9999

9999
0 to
0
1000 h
1
0 to
-

500
Parameter setting
Pr.895 Pr.896 Pr.897 Pr.899
9999
0 to

500
9999
0 to

500
9999
0 to
100%