Shift and removal of a rear side installation frame
One installation frame is attached to each of the upper and lower parts
of the inverter. Change the position of the rear side installation frame
on the upper and lower sides of the inverter to the front side as shown
on the right. When changing the installation frames, make sure that
the installation orientation is correct.
Installation of the inverter
Push the inverter heat sink portion outside the enclosure and fix the enclosure and inverter with upper and lower installation
frame.
Inverter/
Converter unit
NOTE
• Having a cooling fan, the cooling section which comes out of the enclosure cannot be used in the environment of water drops,
oil, mist, dust, etc.
• Be careful not to drop screws, dust etc. into the inverter and cooling fan section.
Installation of the inverter and enclosure design
Enclosure
Inside the
Exhausted air
enclosure
There are finger guards behind the enclosure.
Therefore, the thickness of the panel should be
less than 10 mm (∗1) and also do not place
anything around finger guards to avoid contact
with the finger guards.
Installation
frame
10 mm
Dimension of
Cooling
wind
the outside of
the enclosure
185 mm
Shift
Shift
Enclosure
Finger guard
∗1
140 mm
INSTALLATION AND WIRING
Upper
installation
frame
Lower
installation
frame
31
2