Avoiding The Mechanical Resonance Points (Frequency Jump) - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(H) Protective function parameter
5.10.9
Avoiding the mechanical resonance points
(frequency jump)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these parameters
allow resonant frequencies to be jumped.
Pr.
Name
31
Frequency jump 1A
H420
32
Frequency jump 1B
H421
33
Frequency jump 2A
H422
34
Frequency jump 2B
H423
35
Frequency jump 3A
H424
36
Frequency jump 3B
H425
552
Frequency jump range
H429
3-point frequency jump (Pr.31 to Pr.36)
• Up to three areas may be set, with the jump frequencies set to either the top or bottom point of each area.
• The settings of frequency jumps 1A, 2A, 3A are jump points, and operation is performed at these frequencies in the jump
areas.
Frequency jump
Pr.36
Pr.35
Pr.33
Pr.34
Pr.32
Pr.31
Input set frequency (Hz)
330
PARAMETERS
Initial
Setting
value
range
0 to 590 Hz,
9999
9999
0 to 30 Hz
9999
9999
• [Example 1] To fix the frequency to 30 Hz in the range of 30 Hz to
35 Hz, set 35 Hz in Pr.34 and 30 Hz in Pr.33.
Pr.34: 35 Hz
Pr.33: 30 Hz
• [Example 2] To jump the frequency to 35 Hz in the range of 30 Hz
to 35 Hz, set 35 Hz in Pr.33 and 30 Hz in Pr.34.
Pr.33: 35 Hz
Pr.34: 30 Hz
Description
1A to 1B, 2A to 2B, 3A to 3B are frequency jumps.
(3-point jump)
9999: Function disabled
Set the jump range for the frequency jumps (6-point jump).
3-point jump

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents