Pr.75
setting

14 (initial
Reset command input always enabled.
value), 114
Reset command input enabled only when the
15, 115
protective function activated.
Reset input enabled only when the start signal is
1014, 1114
OFF.
Reset input enabled only when the protective
1015, 1115
function is activated and the start signal is OFF.
16, 116
Reset command input always enabled.
Reset command input enabled only when the
17, 117
protective function activated.
Reset input enabled only when the start signal is
1016, 1116
OFF.
Reset input enabled only when the protective
1017, 1117
function is activated and the start signal is OFF.

When any of "100 to 103, 114 to 117, 1100 to 1103, or 1114 to 1117" is set in Pr.75, the reset limit function is enabled. (The reset limit function is
available for the FR-A860-01440 or higher.)
Reset selection (P.E100)
• When P.E100="1" or Pr.75="1, 3, 15, 17, 100, 103, 115, or 117" is set, reset (reset command via the RES signal or
communication) input is enabled only when the protective function is activated.
• While P.E100 = "2" or Pr.75 = "1000, 1002, 1014, 1016, 1100, 1102, 1114, or 1116", the reset command input is enabled
(using the RES signal or through communication) only when the start signal is OFF.
• While P.E100 = "3" or Pr.75 = "1001, 1003, 1015, 1017, 1101, 1103, 1115, or 1117", the reset command input is enabled
(using the RES signal or through communication) only when the protective function is activated with the start signal OFF.
NOTE
• When the RES signal is input during operation, the motor coasts since the inverter being reset shuts off the output. Also, the
cumulative values of electronic thermal O/L relay and regenerative brake duty are cleared.
• When "reset input always enabled" is selected, the reset key on the PU is enabled only when the protective function is
activated.
• The following table shows applicable start commands. (When both the STF and STR signals are ON, the start signal status is
OFF.
)
Start signal input interface
External terminal
PU
Communication
Reset selection
Applicable start signal
X13, X22, LX, X28, JOGF, JOGR, STF, or STR
Forward/reverse rotation command given by
pressing the FWD/REV key
X13, X22, LX, X28, STF, or STR
(E) Environment setting parameters
Disconnected PU
detection
Operation continues even when
PU is disconnected.
Inverter output shut off when PU
is disconnected.
PU stop selection
The inverter decelerates to a
stop when
is pressed in
any operation mode of the PU,
External, or Network.
245
PARAMETERS
5
GROUP
E