JOG operation in PU
• When the operation panel or parameter unit is in the JOG operation mode, the motor jogs only while the start button is
pressed. (For the operation method, refer to
NOTE
• The reference frequency of the acceleration/deceleration time differs according to the Pr.29 Acceleration/deceleration
pattern selectionsetting. (Refer to
• The Pr.15 setting should be equal to or higher than the Pr.13 Starting frequency setting.
• The JOG signal can be assigned to an input terminal by setting Pr.178 to Pr.189 (Input terminal function selection).
Changing the terminal assignment may affect other functions. Set parameters after confirming the function of each terminal.
• During JOG operation, the second acceleration/deceleration cannot be selected with the RT signal. (Other second functions
are enabled. (Refer to
• When the JOGR or STR signal is input while the JOGF signal is input, the motor is decelerated to stop.
• When the JOGF or STF signal is input while the JOGR signal is input, the motor is decelerated to stop.
• The three-wire type connection is not available for the JOGF and JOGR signals.
• When Pr.79 Operation mode selection="4", JOG operation is started by one push of
and stopped by
• This function is invalid when Pr.79= "3".
• Under the position control, when the position command speed creation is completed and the droop pulse is within in-position
width, the external JOG operation can be operated. (The JOG operation cannot be performed from PU.)
• To perform the JOG operation using the external signals, select the setting of "JOG signal" for the input via terminal JOG in
Pr.291 Pulse train I/O selection. (Refer to
Parameters referred to
???????
Pr.13 Starting frequency
page 283
Pr.20 Acceleration/deceleration reference frequency, Pr.21 Acceleration/deceleration time increments
Pr.29 Acceleration/deceleration pattern selection
Pr.79 Operation mode selection
Pr.178 to Pr.182 (Input terminal function selection)
page
93.)
page
274.)
page
419.))
.
page
308.)
page 274
page 291
page 415
(D) Operation command and frequency command
/
on the operation panel
page 269