Mitsubishi Electric 800 Series Instruction Manual page 46

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Output signal
Terminal
Terminal name
Symbol
A1,
Relay output 1 (fault
B1,
output)
C1
A2,
B2,
Relay output 2
C2
RUN
Inverter running
SU
Up to frequency
OL
Overload warning
Instantaneous power
IPF
failure
FU
Frequency detection
Open collector output
SE
common
For meter
FM
NPN open
collector output
Analog voltage
AM
output
Terminal function description
1 changeover contact output that indicates that an inverter's
protective function has been activated and the outputs are
stopped.
Fault: discontinuity across B and C (continuity across A and
C), Normal: continuity across Band C (discontinuity across A
and C)
1 changeover contact output
Switched to LOW when the inverter output frequency is equal
to or higher than the starting frequency (initial value 0.5 Hz).
Switched to HIGH during stop or DC injection brake operation.
Switched to LOW when the output
frequency is within the set frequency
range 10% (initial value). Switched to
HIGH during acceleration/deceleration
and at a stop.
Switched to LOW when stall prevention
is activated by the stall prevention
function. Switched to HIGH when stall
prevention is canceled.
Switched to LOW when an
instantaneous power failure occurs or
when the undervoltage protection is
activated.
Switched to LOW when the inverter
output frequency is equal to or higher
than the preset detection frequency,
and to HIGH when it is less than the
preset detection frequency.
Common terminal for terminals RUN, SU, OL, IPF, FU
Outputs a selected monitored item
(such as output frequency) among
several monitored items. The signal is
not output during an inverter reset.
The output signal is proportional to the
magnitude of the corresponding
monitoring item.
Use Pr.55, Pr.56, and Pr.866 to set full
scales for the monitored output
frequency, output current, and torque.
page 357
(Refer to
.)
Rated
specification
Contact capacity 230
VAC 0.3 A (power
factor = 0.4)
30 VDC 0.3 A
Permissible load 24
VDC (maximum 27
VDC) 0.1 A
(The voltage drop is
2.8 V at maximum
while the signal is
ON.)
LOW is when the
Fault code (4 bits)
open collector output
output. (Refer to
transistor is ON
.)
page 388
(conducted).
HIGH is when the
transistor is OFF (not
conducted).
Permissible load
Output item:
current 2 mA
Output frequency
For full scale
(initial setting)
1440 pulses/s
This terminal can be
Maximum output
used for open
pulse 50k pulses/s
collector outputs by
Permissible load
setting Pr.291.
current 80 mA
Output signal 0 to 10
VDC, Permissible
Output item:
load current 1 mA
Output frequency
(load impedance 10
(initial setting)
k or more)
Resolution 8 bits
INSTALLATION AND WIRING
Control circuit
Refer
to
page
370
370
370
379
332
515
379
357
2
308
357
45