Mitsubishi Electric 800 Series Instruction Manual page 349

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(M) Monitor display and monitor output signal
Monitor description list (Pr.52, Pr.774 to Pr.776)
• Set the monitor to be displayed on the operation panel and the parameter unit in Pr.52, Pr.774 to Pr.776.
• Refer to the following table to find the setting value for each monitoring. The value in the Pr. setting column is set in each of
the parameters for monitoring (Pr.52, Pr.774 to Pr.776) to determine the monitor item. The value in the RS-485 column is
used for the RS-485 communication special monitor selection. The value in the MODBUS RTU column is used for the
MODBUS RTU real time monitor. (The items marked with "—" cannot be selected. The circle in the negative indication (-)
column indicates that the indication of negative signed numbers is available.)
Increment
Monitor item
and unit
Output frequency/
0.01 Hz/1
speed


0.01 A/
Output current

0.1 A

Output voltage
0.1 V

Fault display
Frequency setting
0.01 Hz/1
value/speed setting

Running speed
1 (r/min)
Motor torque
0.1%
Converter output
0.1 V
voltage
Regenerative brake
0.1%
duty

Electronic thermal
O/L relay load
0.1%
factor
Output current peak
0.01 A/
value
0.1 A

Converter output
0.1 V
voltage peak value
0.01 kW/0.1
Input power
kW

0.01 kW/0.1
Output power

kW

Load meter
0.1%
Motor excitation
0.01 A/
current
0.1 A

Position pulse
Cumulative
1 h
energization time

348
PARAMETERS
Pr. setting
RS-485
1/0/100
H01
2/0/100
H02
3/0/100
H03
0/100
5
H05

6
H06

7
H07

8
H08

9
H09

10
H0A

11
H0B

12
H0C

13
H0D

14
H0E

17
H11
18
H12
19
H13
20
H14
Negative
MODBUS
indication
RTU
(-)

Displays the inverter output
40201

frequency.
Displays the inverter output current
40202
effective value.
40203
Displays the inverter output voltage.
Displays 8 past faults individually.
40205
Displays the set frequency
Displays the motor speed (by the
Pr.37, Pr.144 settings). (Refer to
page
40206

The actual motor speed by encoder
signal is used during encoder
feedback control and vector control.
Displays motor torque as a
percentage (0% under V/F control),
40207
considering the rated torque as
100%.
40208
Displays the DC bus voltage value.
40209
Brake duty set in Pr.30 and Pr.70
Displays the motor thermal
40210
cumulative value, considering the
thermal operation level as 100%.
Saves and displays the output current
40211
monitor peak value.
(Cleared with each start.)
Saves and displays the DC bus
40212
voltage peak value.
(Cleared with each start.)
Displays the power at the inverter
40213
input side.
Displays the power at the inverter
40214
output side.
Displays torque current as a
percentage, considering Pr.56 setting
value as 100% (motor rated torque is
40217
considered as 100% during
Sensorless vector and vector
control).
40218
Displays the motor excitation current
Displays the number of pulses per
motor rotation during orientation
control and position control. (Displays
40219
the voltage monitor when a vector
control compatible option is not
connected.)
Displays the cumulative energization
time since the inverter shipment.
40220
Check how many times the monitor
value exceeded 65535 h with Pr.563.
Description
345)