(G) Control parameters
Setting multiple torque boosts (RT signal, X9 signal, Pr.46, Pr.112)
• When changing the torque boost depending on the usage or when using single inverter switching between multiple motors,
use the second (third) torque boost.
• Pr.46 Second torque boost will become enabled when the RT signal turns ON.
• Pr.112 Third torque boost will become enabled when X9 signal turns ON. Set "9" in Pr.178 to Pr.189 (Input terminal
function selection) to assign X9 signal function to a terminal.
NOTE
• The RT (X9) signal acts as the second (third) function selection signal and makes the other second (third) functions valid.
(Refer to
page
• The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Set a larger value when the distance between the inverter and the motor is long or when there is not enough motor torque in
the low-speed range. It may cause overcurrent trip when it is set too large.
• Setting for Pr.0, Pr.46, and Pr.112 becomes enabled only when the V/F control is selected.
• When the initial value is set in Pr.0, the Pr.0 setting is automatically changed by changing the Pr.71 Applied motor setting.
(Refer to
page
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.3 Base frequency, Pr.19 Base frequency voltage
Pr.71 Applied motor
page 423
Pr.178 to Pr.182 (Input terminal function selection)
590
PARAMETERS
419.)
423)
page 591
page 415