Output Frequency Detection - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.11.7

Output frequency detection

The inverter output frequency is detected and output as output signals.
Pr.
Name
41
Up-to-frequency
M441
sensitivity
42
Output frequency
M442
detection
Output frequency
43
detection for reverse
M443
rotation
50
Second output
M444
frequency detection
116
Third output frequency
M445
detection
865
Low speed detection
M446
870
Speed detection
M400
hysteresis
Output up-to-frequency sensitivity (SU signal, Pr.41)
Set frequency
OFF
ON
SU
Initial value Setting range
10%
0 to 100%
6 Hz
0 to 590 Hz
0 to 590 Hz
9999
9999
30 Hz
0 to 590 Hz
60 Hz
0 to 590 Hz
1.5 Hz
0 to 590 Hz
0 Hz
0 to 5 Hz
• Up to frequency (SU) is output when the output frequency reaches the set
Adjustment
range Pr.41
frequency.
• The Pr.41 value can be adjusted within the range ±1% to ±100%
considering the set frequency as 100%.
• This parameter can be used to check that the set frequency has been
Time
reached, and provide signals such as the operation start signal for related
equipment.
OFF
(M) Monitor display and monitor output signal
Description
Set the level where the SU signal turns ON.
Set the frequency where the FU (FB) signal turns ON.
Set the frequency where the FU (FB) signal turns ON in
reverse rotation.
Same as the Pr.42 setting.
Set the frequency where the FU2 (FB2) signal turns ON.
Set the frequency where the FU3 (FB3) signal turns ON.
Set the frequency where the LS signal turns ON.
Set the hysteresis width for the detected frequency.
379
PARAMETERS
5
GROUP
M