Mitsubishi Electric 800 Series Instruction Manual page 164

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Speed control under Real sensorless vector control, vector control, PM sensorless vector
Adjusting the stall prevention operation signal and output timing (OL
signal, Pr.157)
• If the output torque exceeds the torque limit level and the torque limit is activated, the stall prevention operation signal (OL
signal) is turned ON for 100 ms or longer. When the output torque drops to the torque limit level or lower, the output signal
also turns OFF.
• Pr.157 OL signal output timer can be used to set whether to output the OL signal immediately, or whether to output it after
a certain time period has elapsed.
Pr.157 setting
0
Output immediately.
(Initial value)
0.1 to 25
Output after the set time (s).
9999
Not output.
• The OL signal is also output during the regeneration avoidance operation (overvoltage stall).
NOTE
• OL signal is assigned to the terminal OL in the initial setting. The OL signal can also be assigned to other terminals by setting
"3 (positive logic) or 103 (negative logic)" in any of Pr.190 to Pr.196 (Output terminal function selection).
• Changing the terminal assignment using Pr.190 to Pr.196 (Output terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.22 Stall prevention operation level
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.840 Torque bias selection
page 175
Pr.865 Low speed detection
page 379
Description
Overload state
(OL operation)
OL output signal
Pr.157 Set time(s)
page 332
page 415
page 370
control
163
PARAMETERS
5